MT 200W


MT 200W
Temperature controller device, 4 inputs PT100 probes, 4 relays, Wi-Fi communication, MODBUS-TCP protocol


Dimensions
- Box 90x90x115 mm included terminal blocks
- Front panel 96×96 mm
- Weight 0,4 Kg
Power Supply
- Power supply (24 ÷ 240) Volt AC/DC ± 10% 50/60 Hz without polarity respect, absorption 4 VA
Inputs
- Four analogical inputs, temperature control and mapping with PT100 sensor at three wires inside range from -10°C to +200°C
Outputs
- Four relays 250V AC, 10 A max (resistive load), free switch contact
Communication
- Wifi module with secure access according to GDPR protocol with certificates management, serial number and activation key
- Access point always active for the off-line management
- Access by most popular browser (Safari, Firefox, Chrome)
- No program needed, no app to install
- Timestamp events, with RTC clock and buffer battery
- Whip antenna located on the back of the device
- Remote antenna if needed (optional)
- Access point mode for data download in the absence of internet connection and possible import on cloud
Cloud
- Device management for users and groups
- Remote connection to the cloud
- Reading of temperatures, configurations, thresholds, status, and current alarms
- Event storage with datalogger
- RTC always synchronized with Greenwich time
- Possibility of time zone management
- Current temperature graphs and storage
- Data export in CSV
Characteristics
- Self-extinguishable NORYL Box
- Protection degree front panel in polycarbonate: IP65 (IP66 on request)
- Protection degree of rear panel on terminal board side: IP20
- Display with light segments
- Visualisation of max temperature and the relevant channel in the automatic mode
- Alerts of pre-alarm, alarm, probes fault, fanning, manual function, historic highs
- System programming directly by frontal panel
- Possibility to select independently each channel
- Limit of alarm and pre-alarm settable in the range (-9°C ÷ 199°C)
- Precision ± 1% on full-scale ± 1 digit
- Cooling fan control on three or four channels
- Comparison of temperature for cooling fan between two different levels (L and H)
- Four selectable operating modes
- Detection of fault probes, maximum flexibility of managing and simplicity of programming, checking of validity of the insert data during programming phase
- Continuos storage of planned and reached values by each channel (limits and historic highs)
- Dielectric isolation: 2,5 KV AC for 60”
- Software configuration to control the environment temperature
- Resolution 1°C
- Working temperature of device from -20°C to 60°C
- Max allowed dampness in the room 90% not condensing
- Electrical connections with fast-polarised connectors
- Possibility of manual relays switch through menu test relays to simulate and check the reliability of contact
- Technical manual in five languages (and more on request)
- Construction in accordance to EU and RoHS rules
- Tropicalization (optional)